Honeywell CC-TUIO41 I/O Termination Assembly in stock

Honeywell CC-TUIO41 is the redundant IOTA terminal base for CC-PUIO31 universal I/O module under Experion PKS C300 DCS system.
Send Inquiry

Products Description

Honeywell CC-TUIO41 I/O Termination Assembly in stock


Honeywell CC-TUIO41 is the redundant IOTA terminal base for CC-PUIO31 universal I/O module under Experion PKS C300 DCS system. It provides field wiring terminals, signal conditioning and dual-module hot-standby switching circuit to realize redundant I/O configuration.


Honeywell CC-TUI041(1).jpeg

This conformal coated termination base supports HART signal transmission and channel isolation, matching two CC-PUIO31 cards for redundant operation. It is widely used in petrochemical, refining and power DCS control cabinet spare maintenance.


Honeywell CC-TUI041(6).jpeg

Data Parameters


  • 1. Brand: Honeywell.

  • 2. Model: CC-TUIO41.

  • 3. Product Type: Redundant Universal I/O Termination Assembly (IOTA).

  • 4. Application: Experion PKS C300 DCS distributed control system.

  • 5. Feature: Redundant pair support, HART signal pass-through, channel galvanic isolation.

  • 6. Characteristic: Conformal coating, hot swap support, built-in fault detection circuit.

  • 7. Communication: Field wiring terminal, matched with CC-PUIO31 IOM module.

  • 8. Package: Complete IOTA base with terminal blocks and connection cables.

  • 9. Mounting: Series C I/O rack installation inside DCS control cabinet.

  • 10. Operating Temperature: -40℃ ~ +70℃.

Core Functions


  • 1. Provide field wiring terminals for analog transmitters, digital switches and actuators.

  • 2. Support dual CC-PUIO31 modules to form hot standby redundant I/O group.

  • 3. Transmit HART communication signals between smart field instruments and IOM card.

  • 4. Isolate field interference signals and protect I/O module from surge and short circuit.

  • 5. Complete seamless switchover from primary module to backup module during hardware failure.

Application Scenarios


  • 1. Petrochemical plant Experion PKS DCS redundant I/O cabinet spare replacement.

  • 2. Oil refinery and natural gas processing process control renovation project.

  • 3. Power plant boiler and auxiliary system high-reliability DCS control cabinet.

  • 4. Pharmaceutical and fine chemical hazardous area automation control cabinet.

  • 5. Energy industry redundant universal I/O termination base spare inventory backup.

FAQ


  • 1. Q: What is Honeywell CC-TUIO41?
        A: It is redundant IOTA terminal base used together with CC-PUIO31 universal I/O module.

  • 2. Q: What is the difference between CC-TUIO31 and CC-TUIO41?
        A: CC-TUIO31 is non-redundant base, CC-TUIO41 is redundant version for dual IOM.

  • 3. Q: Can it be used on Safety Manager SIS system?
        A: No, it belongs to Experion PKS DCS hardware, not SIS safety IOTA base.


Leave Your Message


Leave a message